GGD AC low-voltage distribution cabinet

Sitepath:Home > Products > Electrical > Switchgear


GGD AC low-voltage distribution cabinet


Structural characteristics: 

1, GGD-based power distribution cabinet cabinets cabinet to adopt a common form of cold-formed steel frame with 8MF from local welding assembly. GM parts counter module according to the principle of design, and modulus E = 20mm of mounting hole, general-purpose high coefficient. 
2, cabinets designed to take full account of the operation of the cooling problem, upper and lower ends of the cabinets have a different number of cooling slots. 
3, GGD cabinet according to the modern industrial product design requirements, using the method of Golden Section Design cabinets form the various parts of the partition size, so that the entire beautiful cabinets, new look. 
4, doors with axes and hinge-type framework of activities connected to the door of the fold Department has an embedded-type plastic, the closed door and the framework of a certain between the compression stroke, to prevent direct contact with doors and cabinets , also increased the level of protection. 
5, equipped with electrical components of the instrument with multi-unit door and the framework of soft copper wire connected inside the framework of the installation pieces and washers to connect with Knurling, the whole counter a complete protection system grounding. 
6, cabinets-shaped orange polyester topcoat selection of baking finish, strong adhesion, good texture, the whole cabinet was Yaguang hue, to avoid the blinding effect. 
7, cabinets for the protection grade IP30, in accordance with the needs of up to IP40. 

Main technical parameters: 

1, the basic technical parameters 
GGD1: rated voltage AC380V, rated current 400 ~ 1000A, rated short-circuit switch current 15KA, rated short-circuit current tolerance 15KA/1s, rated peak current tolerance 30KA. 
GGD2: rated voltage AC380V, rated current 600 ~ 1500A, rated short-circuit switch current 30KA, rated short-circuit current tolerance 30KA/1s, rated peak current tolerance 63KA. 
GGD3: rated voltage AC380V, rated current 2000 ~ 3150A, rated short-circuit switch current 50KA, rated short-circuit current tolerance 50KA/1s, rated peak current tolerance 105KA. 
2, the main busbar: 1500A rated current and the following in a single copper busbar, 1500A rated current more than double in the copper busbar, busbar surface lining tin lap.